Description
The 3500/65 monitor provides 16 channels of temperature monitoring and accepts both resistance temperature detector (RTD) and isolated tip thermocouple (TC) temperature inputs. The monitor conditions these inputs and compares them against user-programmable alarm setpoints.
The monitor is programmed using the 3500 Rack Configuration Software. You can configure the 16-Channel Temperature Monitor to accept isolated tip thermocouples, 3-wire RTD, 4-wire RTD, or a combination of TC and RTD inputs.
In Triple Modular Redundant (TMR) configurations, you must install temperature monitors in groups of 3 adjacent monitors. In this configuration the monitor uses 2 types of voting to ensure accurate operation and to avoid single-point failures.
Ordering Information
For the detailed listing of country and product specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from Bently.com.
3500/65-AA-BB
A: I/O Module Type
01 RTD/Isolated Tip TC with Internal Terminations
02 RTD/Isolated Tip TC with External Terminations
B: Agency Approval Option
00 None
01 CSA/NRTL/C
02 CSA/ATEX
Agency Approval Option B 02 is only available with Ordering Option A 01.
External Termination Block
172115-01 RTD/Isolated Tip TC External Termination Block (Euro Style connectors).
Cables
3500/65 Transducer (XDCR) Signal to External Termination (ET) Block Cable
134544-AAAA-BB
A: Cable Length
0005 5 feet (1.5 metres)
0007 7 feet (2.1 metres)
0010 10 feet (3 metres)
0025 25 feet (7.5 metres)
0050 50 feet (15 metres)
0100 100 feet (30.5 metres)
B: Assembly Instructions
01 Not Assembled
02 Assembled
Spares
Part Number Description
172931 3500/65 User Guide
145988-02 3500/65 Monitor
172103-01 3500/65 RTD/Isolated Tip TC I/O Module, Internal Terminations
173005 Connector Header, Internal Termination, 20-position, Black
172109-01 3500/65 RTD/ Isolated Tip TC I/O Module, External Terminations
172115-01 RTD/Isolated Tip TC External Termination Block (Euro Style Connectors) Specifications
When replacing an older I/O module with a newer one,172109-01 Rev D, 172103-01 Rev F, 172115-01 Rev E, or future revisions; it is necessary to upgrade the firmware to the monitor with the latest released version. You must remove the I/O module before upgrading the monitor to the latest firmware. Failure to do this will result in an I/O Module Mismatch and 562 ADC Failure in the System Event List.